ses.status.temperature Sensor Warning
Applies to
- ONTAP 9
- AFF A200
- Service Processor (SP)
Issue
- A shelf reports over-temperature
- EMS Logs report:
[node-01: dsa_worker2: ses.status.temperatureWarning:alert]: DS224-12 (S/N SHFFG18330XXXX) shelf X on channel 0x temperature warning for Temperature sensor 11: not installed or failed. Current temperature: 47 C (116 F). This module is on the rear of the shelf at the top left, on shelf module A.
- "
Environment Status
" output:
::> system node run -node <node name> -command environment chassis list-sensors
Channel: 0a
Shelf: 0
SES device path: local access: 0b.00.99
Module type: IOM12E; monitoring is active
Shelf status: non-critical condition
SES Configuration, shelf 0:
logical identifier=0x500a098003bef829
vendor identification=NETAPP
product identification=DS224-12
product revision level=0120
...
Temperature Sensor installed element list: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15; with error: 11
Shelf temperatures by element:
[1] 19 C (66 F) (ambient) Normal temperature range
[2] 22 C (71 F) Normal temperature range
...
[10] 29 C (84 F) Normal temperature range
[11] 173 C (343 F) Overtemperature failure!
[12] 24 C (75 F) Normal temperature range
...
[15] 26 C (78 F) Normal temperature range