System FAN RPM is high and the noise is loud
- Views:
- 1,631
- Visibility:
- Public
- Votes:
- 1
- Category:
- fas-systems
- Specialty:
- HW
- Last Updated:
- 5/1/2025, 7:17:23 AM
Applies to
- FAS System
- AFF System
Issue
- Noise from FAN is loud.
system node environment sensors show
indicates that the FAN speed of the affected node is higher than that of the other nodes.SP-LATEST-
IPMI
log in AutoSupport also indicates that the FAN speed of the affected node is higher than that of the other nodes.
Example:
- The affected node:
FAN1:
Fan1_Status | 0x0 | discrete | Ready | na | na | na | na
Fan1_Current | 7.900 | Amps | ok | 0.000 | 0.500 | 10.000 | 12.000
Fan1_Speed1 | 8400.000 | RPM | ok | 1000.000 | 1250.000 | 9750.000 | 10000.000
Fan1_Speed2 | 8400.000 | RPM | ok | 1000.000 | 1250.000 | 9750.000 | 10000.000
Fan1_Speed3 | 8350.000 | RPM | ok | 1000.000 | 1250.000 | 9750.000 | 10000.000
Fan1_Speed4 | 8400.000 | RPM | ok | 1000.000 | 1250.000 | 9750.000 | 10000.000
Fan1_Volt1 | 11.940 | Volts | ok | 10.560 | 11.160 | 12.840 | 13.440
- Another node:
FAN1:
Fan1_Status | 0x0 | discrete | Ready | na | na | na | na
Fan1_Current | 1.250 | Amps | ok | 0.000 | 0.500 | 10.000 | 12.000
Fan1_Speed1 | 4200.000 | RPM | ok | 1000.000 | 1250.000 | 9750.000 | 10000.000
Fan1_Speed2 | 4250.000 | RPM | ok | 1000.000 | 1250.000 | 9750.000 | 10000.000
Fan1_Speed3 | 4250.000 | RPM | ok | 1000.000 | 1250.000 | 9750.000 | 10000.000
Fan1_Speed4 | 4200.000 | RPM | ok | 1000.000 | 1250.000 | 9750.000 | 10000.000
Fan1_Volt1 | 12.000 | Volts | ok | 10.560 | 11.160 | 12.840 | 13.440
- The amber light of Chassis may be lighted.