SwitchPowerFail_Alert" and"SwitchPsuFanNotOperational_Alert"is reported on the cluster network switches pointing to PowerSupply
::> system health subsystem show
Subsystem Health
----------------- ------------------
SAS-connect ok
Environment ok
Memory ok
Service-Processor ok
Switch-Health degraded
CIFS-NDO ok
Motherboard ok
IO ok
MetroCluster ok
MetroCluster_Node ok
FHM-Switch ok
FHM-Bridge ok
SAS-connect_Cluster ok
13 entries were displayed.::> system health alert showNode: Node-n09Alert ID: SwitchPowerFail_AlertResource: PowerSupply-1Severity: MajorIndication Time: Mon Oct 27 17:23:14 2025Suppress: falseAcknowledge: falseProbable Cause: "PowerSupply-1" on switch "switch1(FOCXXXXXXXX)" is missing or is not operational.Possible Effect: Power supply redundancy on switch "switch1(FOCXXXXXXX)" might be lost.Corrective Actions:
1) Ensure that the power supply units supplying power to the switch are turned on.2) Ensure that the power cord is securely connected to the power supply of the switch.Node: Node-n09Monitor: ethernet-switchAlert ID: SwitchPsuFanNotOperational_AlertAlerting Resource: switch1(FOCXXXXXXXX)/PowerSupply-1 Fan-1Subsystem: Switch-HealthIndication Time: Mon Oct 27 17:23:14 2025Perceived Severity: MajorProbable Cause: Out_of_serviceDescription: "PowerSupply-1 Fan-1" on switch "switch1(FOCXXXXXXXX)" is not functioning properly.Corrective Actions:
1) Use the switch CLI to verify that the fan is functioning at the expected speed.
2) Replace the fan, if it is not operational.Possible Effect: Cooling of switch "switch1(FOCXXXXXXXX)" might be degraded.Acknowledge: FALSESuppress: FALSEPolicy: SwitchPsuFanNotOperational_PolicyAcknowledger:Suppressor:Additional Information:
Switch Name: switch1(FOCXXXXXXXX)
Switch Show Model: N9K-C9336C-FX2
Switch Serial Number: FOCXXXXXXXX
Fan Name: PowerSupply-1 Fan-1
Single Fan or Fan Tray: single
Is PSU Fan: yes
Fan Container Name: PowerSupply-1
Fan Status: not-operational
Successive Warning Count: 943
Error Description: operStatus=3
Switch Fan Resource Status: okAlerting Resource Name: switch1(FOCXXXXXXXX)/PowerSupply-1 Fan-1- EMS logs:
HA Group Notification (Health Monitor process cshm: SwitchPowerFail_Alert[switch1(FOCXXXXXX)/PowerSupply-1]) ALERT- The switch power supply is found to be failed:
::> system switch ethernet power show Admin OperationalSwitch Power Supply Status Status Error------------------ ----------------- ---------- ----------- ---------------Switch1 PowerSupply-1 on failed offEnvPowerSwitch1 PowerSupply-2 on operational- The "
show env" output from switch reports the following:
switch1# show env
Fan:
---------------------------------------------------------------------------
Fan Model Hw Direction Status
---------------------------------------------------------------------------
Fan1(sys_fan1) NXA-FAN-30CFM-F -- back-to-front Ok
Fan2(sys_fan2) NXA-FAN-30CFM-F -- back-to-front Ok
Fan3(sys_fan3) NXA-FAN-30CFM-F -- back-to-front Ok
Fan4(sys_fan4) NXA-FAN-30CFM-F -- back-to-front Ok
Fan_in_PS1 -- -- back-to-front Shutdown
Fan_in_PS2 -- -- back-to-front Ok
Fan Zone Speed: Zone 1: 0x9a
Fan Air Filter : NotSupported
Power Supply:
Voltage: 12 Volts
Power Actual Actual Total
Supply Model Output Input Capacity Status
(Watts ) (Watts ) (Watts )
------- ---------- --------------- ------ ---------- --------------------
1 NXA-PAC-650W-PE 0 W 0 W 0 W Shutdown