How to perform graceful shutdown and power up of all ONTAP nodes in a cluster

Views:
73,287
Visibility:
Public
Votes:
148
Category:
ontap-9
Specialty:
hw
Last Updated:

Applies to

  • ONTAP 9
  • AFF systems
  • FAS systems
  • Excludes MetroCluster configurations

Description

Several events might require a graceful shutdown of ONTAP equipment such as:

  • Scheduled site power outage
  • Data center-wide maintenance
  • Physical system move
  • Preparation for future re-purposing of equipment
Prerequisites
Prior to shutdown
(Best practices)
Identifying hardware components

The ONTAP system is comprised of one or more of the following components. Use the following links for helpful details and images to assist onsite personnel with locating and identifying the equipment.

Procedure

Important: This procedure will shut down all nodes within the cluster and access to data on the cluster will not be possible until the system is powered back up.
  1. Log in to cluster via SSH. Otherwise, log in from any node in the cluster using a local console cable.
  2. Generate a case suppression AutoSupport message for the expected duration of the shutdown event along with any descriptive text:

cluster1::> system node autosupport invoke -node * -type all -message "MAINT=8h Power Maintenance"

  1. Identify the SP/BMC IP address of all nodes:

cluster1::> system service-processor show -node * -fields address
node           address
-------------- ------------
cluster1-01    10.10.10.10
cluster1-02    10.10.10.20
cluster1-03    10.10.10.30
cluster1-04    10.10.10.40

  1. Exit clustershell:

cluster1::> exit

  1. Connect to SP/BMC over SSH using the IP address of any node from Step 3. Otherwise, connect a local console cable to the node. Log in using the same cluster administrator credentials. 

If accessing via the SP/BMC prompt, switch to system console and supply the cluster administrator credentials:

login as: admin
admin@10.10.10.10's password: <password>
SP cluster1-01> system console
Type Ctrl-D to exit.
SP-login: admin
Password: <password>
cluster1::>​​​​

Note: Open an SSH session window to every SP/BMC for monitoring as described in this step.

  1. Halt all nodes in the cluster:

For most cluster configurations:

cluster1::> system node halt -node * -skip-lif-migration-before-shutdown true -ignore-quorum-warnings true -inhibit-takeover true

For clusters with SnapMirror Synchronous operating in StrictSync mode:

cluster1::> system node halt -node * -skip-lif-migration-before-shutdown true -ignore-quorum-warnings true -inhibit-takeover true -ignore-strict-sync-warnings true
  1. Respond to the prompt for each node:

Warning: Are you sure you want to halt node "cluster1-01"?
{y|n}: y

Warning: Are you sure you want to halt node "cluster1-02"?
{y|n}: y

Warning: Are you sure you want to halt node "cluster1-03"?
{y|n}: y

Warning: Are you sure you want to halt node "cluster1-04"?
{y|n}: y

4 entries were acted on.

  1. Wait for each node to halt completely by reaching the LOADER prompt:

LOADER-A>

  1. Connect to each node in the cluster via SP/BMC (if not already connected) or using a local console cable and confirm each node is at the LOADER prompt (as in Step 8).
Physical activity
The physical activity here ensures no equipment damage occurs while the system is powered down and ensures the correct order of equipment startup is followed, so that the ONTAP system is prepared to serve data after the event is complete.
  1. Toggle each PSU rocker switch to the OFF position on each piece of equipment.

Note: Some PSUs do not have rocker switches.

  1. Remove the power cable connecting each PSU to the PDU.
  2. Visually confirm each component has successfully powered off.
  3. Ensure that all controllers, disk shelves, and switches associated with the cluster are powered down.
Power up

When the system is ready to be powered back up following the steps in How to power up all ONTAP nodes in a cluster following a graceful shutdown

Additional Information

Tips

To power off a controller remotely:

SP/BMC> system power off
This will cause a dirty shutdown of your appliance.  Continue? [y/n] y
SP/BMC> system power status
Chassis Power is off

The warning can be ignored only after a clean shutdown and the node is at the LOADER prompt. Any other use can cause loss of data.

Repeat from other SP or BMC in the same chassis (where applicable).

 

Sign in to view the entire content of this KB article.

New to NetApp?

Learn more about our award-winning Support

NetApp provides no representations or warranties regarding the accuracy or reliability or serviceability of any information or recommendations provided in this publication or with respect to any results that may be obtained by the use of the information or observance of any recommendations provided herein. The information in this document is distributed AS IS and the use of this information or the implementation of any recommendations or techniques herein is a customer's responsibility and depends on the customer's ability to evaluate and integrate them into the customer's operational environment. This document and the information contained herein may be used solely in connection with the NetApp products discussed in this document.