RTC Battery Fault
Applies to
- FAS/AFF Platforms
- Real-time clock (RTC) coin-cell battery
Issue
- Node and chassis fault LEDs are illuminated with error below:
hsamcmd --fault-show-all
===============================
tag origin fld fault reason count time
---- ------- ---- ------------- ------ -----
1 bmc /chassis-1/controller-a P3V3_BATT: Voltage Sensor 26 LNC 1 Wed Jun 25 10:58:10 2025
2 bmc /chassis-1/controller-a P3V3_BATT: Voltage Sensor 26 LCR 1 Wed Jun 25 10:58:22 2025
- Or node and chassis fault LEDs are illuminated with no clear indication of the fault
- The following EMS message is generated, and a non-critical fault will be reported against the battery:
Tue Sep 4 15:05:29 CEST [NODE1:monitor.chassisPower.degraded:warning]: Chassis power is degraded: RTC Battery is in WARN LOW state current voltage is 2774 mV, normal low is 2800 mV
SP-LATEST-IPMI
log showsP3.3V Batt
is the the following condition.
P3.3V Batt warnlow 2660 mV 2537 mV 2695 mV 3307 mV 3447 mV
Or
P3.3V Batt critlow 945 mV 2100 mV 2205 mV 3395 mV 3500 mV
SP-LATEST-SYSLOG
log showsrtcWarnLowPower
BMC env_mgr[1534]: Payload EMS: EMS_monitor_rtcWarnLowPower(2660 mV)
- BMC
events all
showsP3.3V Batt is critical low
.
BMC env_mgr[1461]: P3.3V Batt is critical low
- From the BMC/SP shows
P3V_BAT
is the following condition:
Sensor Name | Current | Unit | Status | LCR | LNC | UNC | UCR
-----------------+------------+------------+------------+-----------+-----------+-----------+-----------
P3V_BATT | 2.840 | Volts | nc | 2.720 | 2.880 | 3.300 | 3.460
Or
P3V3_BATT | 0.963 | Volts | cr | 2.100 | 2.205 | 3.395 | 3.500