Overtemperature lead SHELF FAULT alert
Applies to
- AFF / ASA / FAS
- DS2246
- ONTAP 9
Issue
EMS log
showSHELF_FAULT
error:
[FAS-01: dsa_worker0: ses.status.temperatureWarning:alert]: DS2246 (S/N XXXXXXXXXXX) shelf 5 on channel 0b temperature warning for Temperature sensor 6: non-critical status; overtemperature warning. Current temperature: 66 C (150 F). This module is on the rear of the shelf on the lower right power supply.
[FAS-01: statd: monitor.shelf.warning:error]: Fault reported on disk storage shelf attached to channel 0b. Check fans, power supplies, disks, and temperature sensors.
[FAS-01: statd: callhome.shlf.fault:error]: Call home for SHELF_FAULT
STORAGE-FAULT
of ASUP log:
Enclosure Status: non-critical
Channel: 0b
Shelf: 5
Shelf Type: DS2246
...
Temperature Sensors:
Element Status Status Bytes Status Descriptions
1: OK 01,00,36,00
2: OK 01,00,3A,00
3: OK 01,00,3D,00
4: OK 01,00,53,00
5: OK 01,00,3C,00
6: NONCRITICAL 03,00,56,04 OT WARNING
7: OK 01,00,3E,00
8: OK 01,00,3F,00
ENVIRONMENT
of ASUP log:
Temperature Sensor installed element list: 1, 2, 3, 4, 5, 6, 7, 8; with error: 6
Shelf temperatures by element:
[1] 34 C (93 F) (ambient) Normal temperature range
[2] 38 C (100 F) Normal temperature range
[3] 41 C (105 F) Normal temperature range
[4] 63 C (145 F) Normal temperature range ------------------> sensor in PSU1
[5] 40 C (104 F) Normal temperature range
[6] 66 C (150 F) Overtemperature warning!-------------------> sensor in PSU2
[7] 41 C (105 F) Normal temperature range
[8] 42 C (107 F) Normal temperature range