Can NS224 be connected to both 100V and 200V PDUs simultaneously during power cable replacement?

Views:
22
Visibility:
Public
Votes:
0
Category:
not set
Specialty:
not set
Last Updated:

Applies to

  • NS224 shelf
  • Environment: Power Distribution Units (PDUs) with different voltages (100V and 200V)

Answer

No, it is not recommended to connect NS224 to PDUs with different voltages (e.g., 100V and 200V) simultaneously, even temporarily.

Additional Information

  • The NS224 power supply units (PSUs) are designed to operate within a wide voltage range of 100V to 240V, meaning they can function with either 100V or 200V.
  • However, connecting the system to PDUs with different voltages at the same time can create risks such as potential voltage differences, ground loops, and abnormal currents.
  • To avoid these risks, it is advised to perform the power cable replacement while the system is offline.
  • Ensure the system is powered down before switching to a different voltage PDU.

 

NetApp provides no representations or warranties regarding the accuracy or reliability or serviceability of any information or recommendations provided in this publication or with respect to any results that may be obtained by the use of the information or observance of any recommendations provided herein. The information in this document is distributed AS IS and the use of this information or the implementation of any recommendations or techniques herein is a customer's responsibility and depends on the customer's ability to evaluate and integrate them into the customer's operational environment. This document and the information contained herein may be used solely in connection with the NetApp products discussed in this document.