AFF C30 shuts down due to critical temperature alerts
Applies to
AFF C30
Issue
- Both nodes detected critical temperature conditions and shut down automatically during system configuration.
-
The ambient temperatures measured at the front air intake and rear exhaust were 21.7°C and 26.2°C, respectively.
-
Internal sensors
Amb_temp_1andAmb_temp_2reported approximately 43°C with the front bezel attached, but the readings dropped to approximately 22°C when the bezel was removed. -
The NetApp logo light on the front bezel was initially off and turned on and off when the bezel was touched.
-
Both the temperature readings and logo light behavior changed when the left side of the bezel was pressed.
-
Replacing the front bezel did not resolve the temperature abnormalities or the logo light issue.
-
The following temperature-critical shutdown events were recorded in the BMC logs of both nodes:
[IPMI.emergency]: env_mgr triggers OS halt:Temperature critical[Controller.notice]: Appliance user command halt.[IPMI Event.critical]: System power down[IPMI.notice]: Assertion Event, "Storage OS graceful shutdown"[IPMI.emergency]: Data ONTAP initiated shutdown