CHW-3318: PSU unit shows sensors "not-available" before and after replacement. PSU is confirmed to be good
Issue
The PSU2 unit reports "not-available" sensors when attempting to retrieve system sensors information from BMC and ONTAP prompts.
- When reviewing the outputs for system sensors of the affected node it shows the PSU sensors as being "not-available":
BMC affected-node-name> system sensors show
PSU1:
PSU1_Status      | 0x0        | discrete   | Ready      | na | na        | na        | na
PSU1_12V_IOUT    | 32.000     | Amps       | ok         | 0.000     | 0.000     | 165.000   | 173.000
PSU1_12V_VOUT    | 12.060     | Volts      | ok         | 10.980    | 11.400    | 12.900    | 13.500
PSU1_IIN         | 1.800      | Amps       | ok         | 0.000     | 0.000     | 14.100    | 15.000
PSU1_PIN         | 424.000    | Watts      | ok       | na        | na        | na        | na
PSU1_POUT        | 392.000    | Watts      | ok         | na        | na        | na        | na
PSU1_Type        | 2.000      | unspecified | ok         | na        | na        | na        | na
PSU1_VIN         | 228.000    | Volts      | ok         | 84.000    | 90.000    | 264.000   | 276.000
PSU2:
PSU2_Status      | na         | discrete   | na         | na        | na        | na        | na
PSU2_12V_IOUT    | na         | Amps       | na         | 0.000     | 0.000     | 165.000   | 173.000
PSU2_12V_VOUT    | na         | Volts      | na         | 10.980    | 11.400    | 12.900    | 13.500
PSU2_IIN         | na         | Amps       | na         | 0.000     | 0.000     | 14.100    | 15.000
PSU2_PIN         | na       | Watts      | na         | na        | na        | na        | na
PSU2_POUT        | na         | Watts      | na         | na        | na        | na        | na
PSU2_Type        | na         | unspecified | na         | na        | na        | na | na
PSU2_VIN         | na         | Volts      | na         | 84.000    | 90.000    | 264.000   | 276.000
::> system node environment sensors show -node affected-node-name  -state !normal
Node Sensor                 State Value/Units Crit-Low Warn-Low Warn-Hi Crit-Hi
---- --------------------- ------ ----------- -------- -------- ------- -------
affected-node-name
     PSU2 Present          not-available
     PSU2 Output OK        not-available
     PSU2 Input OK         not-available
     PSU2 In Volt          not-available
                                        - mV     84000    90000  264000  276000
     PSU2 In Curr          not-available
                                        - mA         0        -   14100   15000
     PSU2 12V Out Volt     not-available
                                        - mV     10980    11400   12900   13500
     PSU2 12V Out Curr     not-available
                                        - mA         0        -  165000  173000
     PSU2 In Pwr           not-available
                                        - W          -        -       -       -
     PSU2 Out Pwr          not-available
                                        - W          -        -       -       -
     PSU2 Type             not-available
10 entries were displayed.
- Replacement PSU continues to display the same results
- System Health commands show the cluster as healthy
- Swapping PSU with a known-working unit from partner node indicates that the both PSU units are good, but the error remains in the PSU slot.