CFBMC-8337: Inlet ODP Temp thresholds change during an ONTAP reboot
Issue
- Applies to:
- AFF A1K, AFF A90, AFF A70, AFF C80
- AFX 1K, AFX 2K
- ASA A1K, ASA A90, ASA A70
- FAS90, FAS70
- After a node reboots ONTAP the warning high and critical high values of Inlet ODP Temp sensors show as 35C and 40C instead of 42C and 47C for a few minutes:
Sensor Name State Current Critical Warning Warning Critical
Reading Low Low High High
-------------------------------------------------------------------------------------------------
Inlet ODP Temp1 normal 32 C 0 C 3 C 35 C 40 C
Inlet ODP Temp2 normal 32 C 0 C 3 C 35 C 40 C
- After the BMC has synchronized with ONTAP, the temperature threshold typically revert back to the 42C and 47C values
- This threshold change might cause chassis "over temperature" alerts if the system is running close to the 35C "Warning High" threshold.