DS212 shelf reports DC FAIL on both PSUs
Applies to
- ONTAP 9
- DS212 disk shelf
- IOM12
- Power Supply Unit (PSU)
Issue
- AutoSupport has detected a
"SHELF POWER INTERRUPTED"event. - Both power supply units (PSUs) on the same disk shelf report errors:
- Environment status reports:
=== ENVIRONMENT ===Channel: 0aShelf: 2SES device path: local access: 0a.02.99Module type: IOM12B; monitoring is activeShelf status: critical conditionPower Supply installed element list: 1, 2; with error: 1, 2Power Supply information by element:[1] Serial number: PSQ094231902539 Part number: 114-00148+G1Type: 7DInput voltage: <N/A>Firmware version: 0112 Swaps: 0[2] Serial number: PSQ094231902542 Part number: 114-00148+G1Type: 7DInput voltage: <N/A>Firmware version: 0112 Swaps: -
storage show faultshows PSU isCRITICAL.=== STORAGE-FAULT ===Enclosure Status: criticalChannel: 0aShelf: 2Shelf Type: DS212-12Product Serial Number: SHJSG2343000296Module Type: IOM12BPower Supplies:Element Status Status Bytes Status Descriptions1: CRITICAL 02,00,00,F1 DC FAIL, OFF, RQSTED ON, FAIL2: CRITICAL 02,00,00,F1 DC FAIL, OFF, RQSTED ON, FAIL
- External rack power supply and PSU power cables show no issue.
- Baseboard Management Controller (BMC) restart does not clear the PSU status.
- Takeover and giveback do not clear the PSU status.
- Reseating PSU 1 and PSU 2 does not clear the status.
- PSU attention LEDs illuminate amber after the PSUs are reseated.