Fail to retrieve BMC sensor value during BBU firmware auto upgrade
Applies to
- ONTAP 9
- AFF-A20
- AFF-A30
- AFF-A50
- AFF-C30
- AFF-C60
- BMC firmware 19.3
Issue
- ONTAP reports
system node environment sensors showcommand fail after BMC firmware upgrade to 19.3 successfully.
Cluster::> system node environment sensors show
Warning: Unable to list entries on node node01. Failed to list sensor info from BMC
SP-LATEST-SYSTEM-EVENT-LOGreportsBBU FW upgradedafter BMC firmware upgrade complete.
Record 1135: Wed Dec 10 05:29:11.038592 2025 [BMC.notice]: BMC reset initiated by storage controllerRecord 1152: Sun Jan 01 00:02:05.188664 2017 [BMC.notice]: Running primary version 19.3Record 1156: Sun Jan 01 00:02:18.322473 2017 [BMC.normal]: Heartbeat startedRecord 1160: Wed Dec 10 05:32:40.098169 2025 [IPMI.notice]: 03bb | 02 | EVT: 6f0580ff | Sensor 255 | Assertion Event, "Timestamp Clock Sync"Record 1183: Wed Dec 10 05:42:26.009913 2025 [BMC.notice]: BBU FW is upgraded
SP-MGMT-MLOG-TXT.GZreports sensor error:
[kern_servprocd:info:8169] 0x80ad45600: 8003e800001d5a9d: ERR: Servprocd::bmc_client: bmc_get_sensor_info_imp: target_node=<NODE>, err=Failed to list sensor info from BMC
- After BBU(NVMEM Battery) firmware upgrade complete
system node environment sensors showcommand succeed.