FAS8700/FAS8300/AFF A400 reports "Chassis temperature is too cold" ERROR
Applies to
- AFF A400, AFF C400
- ASA A400, ASA C400,
- FAS8300, FAS8700
- ONTAP 9
Issue
Error messages for "Chassis temperature is too cold" on both nodes with a subsequent environmental shutdown.
Example:
17:42:11 node1 ALERT monitor.chassisTemperature.cool: Chassis temperature is too cool: LED1 Temp is warning low (3 C).
17:42:11 node1 ERROR monitor.shutdown.chassisUnderTemp: Chassis temperature is too cold: Ambient temperature is low. System will be shutdown in 2 minutes
17:42:11 node2 ALERT monitor.chassisTemperature.cool: Chassis temperature is too cool: LED1 Temp is warning low (3 C).
17:42:11 node2 ERROR monitor.shutdown.chassisUnderTemp: Chassis temperature is too cold: Ambient temperature is low. System will be shutdown in 2 minutes
17:41:03 node2 ALERT monitor.chassisTemperature.cool: Chassis temperature is too cool: MP Temp3 is warning low (5 C).
17:41:01 node1 ALERT monitor.chassisTemperature.cool: Chassis temperature is too cool: MP Temp3 is warning low (5 C).