EMS reports "Chassis power supply is degraded" followed " Service Processor cannot obtain network configuration using DHCP"
Applies to
- Service Processor (SP)
- Baseboard Management Controller (BMC)
- Power supply unit (PSU)
Issue
- EMS reports SP error before PSU error.
Example:
Mon Oct 19 00:35:39 +0800 [node-01: servprocd: sp.dhcp.failure:error]: Service Processor cannot obtain network configuration using DHCP.
- EMS reports chassis power supply is degraded.
Example:
[?] Mon Oct 19 00:38:10 +0800 [node-01: env_mgr: monitor.chassisPowerSupply.degraded:notice]: Chassis power supply 2 is degraded: PSU2 Power Out is Unreadable
[?] Mon Oct 19 00:38:10 +0800 [node-01: env_mgr: monitor.chassisPowerSupply.degraded:notice]: Chassis power supply 2 is degraded: PSU2 Curr Out is Unreadable
[?] Mon Oct 19 00:38:10 +0800 [node-01: env_mgr: monitor.chassisPowerSupply.degraded:notice]: Chassis power supply 2 is degraded: PSU2 Volt Out is Unreadable
[?] Mon Oct 19 00:38:10 +0800 [node-01: env_mgr: monitor.chassisPowerSupply.degraded:notice]: Chassis power supply 2 is degraded: PSU2 Power In is Unreadable
[?] Mon Oct 19 00:38:11 +0800 [node-01: env_mgr: monitor.chassisPowerSupply.degraded:notice]: Chassis power supply 2 is degraded: PSU2 FAN is Unreadable
[?] Mon Oct 19 00:38:11 +0800 [node-01: env_mgr: monitor.chassisPowerSupply.degraded:notice]: Chassis power supply 2 is degraded: PSU2 Curr In is Unreadable
[?] Mon Oct 19 00:38:11 +0800 [node-01: env_mgr: monitor.chassisPowerSupply.degraded:notice]: Chassis power supply 2 is degraded: PSU2 Volt In is Unreadable
- The chassis PSU is good by manual checking.