Chassis Warning C4-1006 and Critical C4-1010 Message reported on Brocade switch
Applies to
- Brocade DCX
- X6 directors
IssueFormat
- One of the port blade on the switch went to disabled state with below errors reported under errdump :
2020/01/22-19:07:06, [C4-1010], 433, SLOT 2 | CHASSIS, CRITICAL, DCX, S12,C0: Above normal hardware errors were observed: fault1:0x1, fault2:0x64 thresh2:0xb0000064.
2020/01/22-19:20:41, [C4-1006], 434, SLOT 2 | CHASSIS, WARNING, DCX, S12,C0: Various non-critical hardware errors were observed: fault1:0xa, fault2:0x64 thresh1:0xa000000a.
- In the example above, the error is being reported by slot 2 CP which is monitoring the switch but it is reporting an issue on blade on slot 12(S12) chip 0.
HAshow
reports current active CP as slot 2:
Local CP (Slot 2, CP1): Active, Warm Recovered
Remote CP (Slot 1, CP0): Standby, Healthy
HA enabled, Heartbeat Up, HA State synchronized
slotshow -m
shows he blade on affected slot ( here slot 12 as per the above log snippet) as healthy.
slotshow -m:
Slot Blade Type ID Model Name Status
--------------------------------------------------
1 CP BLADE 175 CPX6 ENABLED
2 CP BLADE 175 CPX6 ENABLED
3 SW BLADE 178 FC32-48 ENABLED
4 SW BLADE 178 FC32-48 ENABLED
5 SW BLADE 178 FC32-48 ENABLED
6 SW BLADE 178 FC32-48 ENABLED
7 CORE BLADE 177 CR32-8 ENABLED
8 CORE BLADE 177 CR32-8 ENABLED
9 SW BLADE 178 FC32-48 ENABLED
10 SW BLADE 178 FC32-48 ENABLED
11 SW BLADE 178 FC32-48 ENABLED
12 SW BLADE 178 FC32-48 ENABLED