Temperature sensor 3 PSU 1 Inlet Alert
Applies to
- FAS systems
- AFF systems
- Disk shelves
Issue
- Inlet temp on PSU1 was reading temp that was outside/below Low temp threshold.
- PSU2 temp was right at the bottom of the temperature range, just not low enough to set an alert.
Mon Nov 02 08:54:00 EST [cluster1-A: monitor: monitor.globalStatus.critical:EMERGENCY]: Disk shelf fault.
Mon Nov 02 08:54:21 EST [cluster1-A: power_low_monitor: monitor.chassisPower.degraded:alert]: Chassis power is degraded: Power Supply Status Critical: PSU1.
Mon Nov 02 08:54:21 EST [cluster1-A: power_low_monitor: callhome.chassis.power:error]: Call home for CHASSIS POWER DEGRADED: Power Supply Status Critical: PSU1.
Temperature Sensor installed element list: 1, 2, 3, 4, 5, 6, 7, 8; with error: 3
Shelf temperatures by element:
[1] 12 C (53 F) (ambient) Normal temperature range
[2] 14 C (57 F) Normal temperature range
[3] 9 C (48 F) Undertemperature warning!
[4] 34 C (93 F) Normal temperature range
[5] 10 C (50 F) Normal temperature range
[6] 43 C (109 F) Normal temperature range
[7] 22 C (71 F) Normal temperature range
[8] 24 C (75 F) Normal temperature range